VFT performance of a 180/110 mm co-axial gap in SF6 up to 4 bar absolute

Nielsen, Shawn, Jan, Reynders, & Jandrell, Ian (1999) VFT performance of a 180/110 mm co-axial gap in SF6 up to 4 bar absolute. In 11th International Symposium on High-Voltage Engineering (ISH 99), Institution Of Electrical Engineers, Stakis Metropole Hotel, London, United Kingdom, pp. 1-201.

View at publisher

Abstract

Disconnector switch operation in GIS generates VFT voltages in the system. It is important, for insulation co-ordination purposes, to obtain accurate VFT V-t data for typical gap geometries found in GIS. This paper presents experimentally obtained VFT V-t data for a 180/1 lOmm co-axial gap. The VFT has a time to first peak of 35 ns and a oscillation frequency of 13,6 MHz. Due to the location of the voltage divider in a compartment adjacent to the gap, a correction factor of 1.1 is used to relate the measured breakdown voltage to that in the gap. Positive polarity VFT V-t data is presented for 1, 2, 3 and 4 bar absolute and negative polarity VFT data for 3 and 4 bar absolute. Two methods of generating the VFT's are used. The first is to power up the test transformer at power frequency. The second is to generate a switching impulse by discharging a capacitor into the primary of the test transformer.

Impact and interest:

0 citations in Scopus
Search Google Scholar™

Citation counts are sourced monthly from Scopus and Web of Science® citation databases.

These databases contain citations from different subsets of available publications and different time periods and thus the citation count from each is usually different. Some works are not in either database and no count is displayed. Scopus includes citations from articles published in 1996 onwards, and Web of Science® generally from 1980 onwards.

Citations counts from the Google Scholar™ indexing service can be viewed at the linked Google Scholar™ search.

Full-text downloads:

11 since deposited on 20 Aug 2015
2 in the past twelve months

Full-text downloads displays the total number of times this work’s files (e.g., a PDF) have been downloaded from QUT ePrints as well as the number of downloads in the previous 365 days. The count includes downloads for all files if a work has more than one.

ID Code: 86676
Item Type: Conference Paper
Refereed: No
Additional Information: (Conf. Publ. No. 467), Volume: 1
Keywords: VFT performance, insulation co-ordination purposes, disconnector switch operation
DOI: 10.1049/cp:19990542
ISBN: 9780852967195
Divisions: Current > Schools > School of Electrical Engineering & Computer Science
Current > QUT Faculties and Divisions > Science & Engineering Faculty
Copyright Owner: Copyright 1999 Please consult the author.